EPR - SHIELDED - 35KV

Legend:  A: Conductor    B: Semicon Conductor Shielding     C: EPR Insulation
D: Semicon Layer     E: Metallic Shielding     F: Binder Tape     G: Jacket

Applications

  • 90°C conductor temperature, wet or dry, continuous operation.
  • Aerial (messenger supported) as P-193
  • Direct burial
  • Conduits or ducts
  • Open wiring indoors
  • Single conductor size 250 kcmil and larger may be installed in cable tray per NEC 318-2(b) and marked "for CT use" when specifically ordered.
  • Dry locations
  • Wet locations
  • Exposure to weather
  • In presence of many chemicals and oils
  • Exposure to ozone

Note: When required this cable shall meet AEIC CS-6 requirements.

U.L. listed as type MV-90, U. L. Standard 1072 for use in accordance with article 310-6 N.E.C.