TEMPERATURE RATINGS
AND OVERLOADS
Temperature Ratings The
temperature ratings of power cables refer to the actual
conductor temperature, not to a rise above ambient
temperature, as is the practice with some equipment
ratings. The allowable conductor temperature is established
by the ability of the nonmetallic components of the
cable - insulation, polymeric part of the shielding
system, and the jacket - to withstand elevated temperatures
for certain periods of time.
Time enters into consideration
for two reasons. First, thermal degradation is a chemical
process that inescapably involves time. Second, the
conduction of heat through a material is not instantaneous.
It requires time to transfer heat from the cable conductor
to the cable surface where it can be dissipated into
the environment.
Most of the heat that
is generated in a power cable is the result of power
losses that occur because of current flow in the conductor.
The conductor usually attains the highest temperature
of any of the cable components.
It is not surprising
then that power cables carry three temperature ratings
(established somewhat arbitrarily on the basis of
some laboratory data and field experience) and each
of these ratings involves time.
1. The normal or service
rated temperature of a cable does not carry a specified
time element, but cables are expected to operate many
years at that temperature. Experience and laboratory
investigations indicate that at or below this temperature,
no significant temperature dependent deterioration
will occur during a reasonable service life.
2. The emergency overload
temperature rating of rubber and plastic insulated
power cables involves a time limitation of not more
than 100 hours at that temperature in any consecutive
twelve-month period, and not more than 500 hours at
that temperature during the service life of the cable.
3. The short-circuit
temperature rating of a cable is associated with times
that are measured in fractions of a second. Power
systems are usually capable of delivering many times
their rated current to a system short-circuit. To
minimize damage, systems are usually equipped with
overcurrent protective devices that will interrupt
the flow of fault current in a few cycles. For example,
if the flow of fault current in a 60 Hz system is
interrupted in 10 cycles, the time involved is 10/60
or 0.167 seconds. Seldom are well designed power systems
permitted to carry short-circuit currents continuously
for as long as one second.
Short-circuit currents
are so large that they are capable of raising conductor
temperatures almost instantaneously but the current
exists for such a short time that there is little
opportunity for the insulation to conduct the heat
from the conductor during the period of the fault.
Hence, it does require some time after the fault for
the cable to dissipate the heat surge and regain its
normal thermal state. Overloads Any conductor current
that results in the conductor temperature exceeding
its normal rated value is an overload. An overload
situation can develop in several ways:
1. The conductors may be undersized
for the ampere loading in the particular thermal environment.
2. The connected load or its load factor may increase
more than anticipated
3. The thermal environment may be changed after the
cables are installed. For example:
· Directly buried or duct circuits
may produce sufficient heat to dry the surrounding
soil, thereby increasing the soil thermal resistivity,
resulting in increased conductor temperatures at
the same ampere loading.
· Installation of additional power cables in previously
empty ducts may cause an excessive increase in duct
bank temperature.
· Additional cables may be added to cable trays,
increasing the amount of heat and limiting the circulation
of cooling air.
· Thick fire-stops in cable trays may seriously
interfere with heat dissipation from cables.
· Steam Lines increase ambient temperature near
the cable circuits.
· The surface above an underground circuit may be
paved.
4. Electrically paralleled cables
may not share the load equally because of impedance
imbalance.
5. The available fault current from the power systems
may be greater than that anticipated during the cable
circuit design.
6. Fuses, or relays and circuit breakers may not function
properly.